Components

VDR for Three Phase Meter

VDR for Three Phase Meter

MYN23-821K1. Maximum allowable voltage AC: 510 Vrms; DC: 670 V. Average power dissipation ≥1.0 W. Varistor voltage 820V±10%. Clamping voltage ≤1355V.
Chat on WhatsApp
Introduction

Introduction

Product Details

MYN23·821K

Technical Parameters:

ParameterSpecificationTest Condition
Maximum allowable voltageAC: 510 Vms
DC: 670 V
Average power dissipation>1.0 W
Varistor voltage820V±10%Test current: 1mADC
Clamping voltage≤1355VTest waveform: 8/20μs
Test current: 100 A
Maximum surge current10000 A≥1 timeTest waveform: 8/20 μs
Interval between two surges: 5 min
8500 A≥2 times
3000 A≥100 times

Datasheets

Interested in our products ?

Our professional sales team are waiting for your consultation.