Monofásico

Electronic Energy Meter Module
Electronic Energy Meter
The CA168 - T01 is an electronic energy meter featuring a replaceable battery. It is equipped with a wheel - display and programming buttons. The meter is designed to operate at 230V, with a current rating of 5(80)A and a frequency of 50HZ. It supports multiple communication methods, namely RF, LoRa, LoRaWAN, PLC/G3PLC.
Introducción
Introducción
Características principales
- Replaceable battery
- Wheel - display and programming buttons
- Operates at 230V, 5(80)A, 50HZ
- RF, LoRa, LoRaWAN, PLC/G3PLC communication support
- Anti - electricity - stealing function
- DLMS certification
- Precise measurement
- Stable performance under normal conditions
- This meter is well - suited for both commercial and residential electricity measurement needs. The replaceable battery ensures continuous operation with easy battery replacement. The wheel - display and programming buttons offer user - friendly operation. The multiple communication options enable seamless integration into different smart grid systems. The anti - electricity - stealing function safeguards the integrity of electricity measurement, and the DLMS certification attests to its compliance with international standards.
The CA168 - T01 is an electronic energy meter featuring a replaceable battery. It is equipped with a wheel - display and programming buttons. The meter is designed to operate at 230V, with a current rating of 5(80)A and a frequency of 50HZ. It supports multiple communication methods, namely RF, LoRa, LoRaWAN, PLC/G3PLC.
Parameters
| Electrical parameters: | ||
| Voltage | ||
| Nominal voltage Un | 230V | |
| Limited voltage | 50%~130%Un | |
| Frequency | ||
| Nominal frequency fn | 50-60Hz | |
| tolerance | 5% | |
| Current | ||
| Basic current(Ib) | 5A | |
| Maximum current(Imax) | 60A (100A optional) | |
| Starting current(Ist) | 20mA | |
| Active energy constant | 1000imp/kWh | |
| Measurement Accuracy | ||
| Active energy to IEC62053-21 | Class1.0 | |
| Burden | ||
| Voltage circuit | <2W <8VA | |
| Current circuit | <1VA | |
| Temperature range | ||
| Operation meter | -25℃ to+70℃ | |
| Storage | -40℃ to+85℃ | |
| Insulation | ||
| Insulation level | 4kV rms 1min | |
| Voltage impulse withstand | 8kV 1.2/50 μs | |
| Insulation System Classification | Protective Class II | |
| Electro Magnetic Compatibility | ||
| Electrostatic discharges | ||
| Contact discharge | 8kV | |
| Air discharge | 16kV | |
| Electromagnetic RF fields | ||
| 27MHz to 500MHz typical | 10V/m | |
| 100kHz to 1GHz typical | 30V/m | |
| Fast transient burst test | 4kV | |
| Mechanical requirements | ||
| Meter shell Protection Rate | IP54 | |
| Insulation System Classification | Protective Class II | |
| Maximum cable size | 8 mm | |