Monofásico

CA168-SF01
Single Phase Compact Din Rail Electricity Meter
CA168-SF01 is our new generation of Din-rail single-phase electricity meter, with accuracy of Class 1,and its shell is made of polycarbonate flame retardant material.This meter is equipped with a current isolation wire and also supports dual circuit measurement and relays to bring outstanding tamper detection features. The communication with the external keypad(ClU) can be done with either PLC, RF, or by Cable connection. Its installation requirements are also optional.
Introdução
Introdução
Principais recursos
- .Multi-Tariff
- DLMS/COSEM
- STS prepayment
- 20 digits STS encryption
- Tamper detection and record
- LoraWan centralized collecting
- Slim-line and space-economy design
- Disconnect on overload and no credit
- Programmable load limit and low credit warning
- Infrared port/RS485/virtual token carrier(optional)Surge protection for lightening and other line surges
- Up to 13kV/6.5kA surge protection for lightening and other line surges
- CIU by PLC/RF/ Cable (optional)
Split Configuration for Increased Revenue Protection
The CIU (Customer Interface Unit) is optional. The MCU (Metering & Control Unit) and CIU is linked via Mbus 2 wires communication, galvanically-isolated PLC or RF wireless communication, the communication method is on request.
The CIU is installed within consumer’s home, while MCU is installed in a meter cabinet away from consumers.
Parameters
| Electrical parameters: | ||
| Voltage | ||
| Nominal voltage Un | 230V | |
| Limited voltage | 70%~120%Un | |
| Frequency | ||
| Nominal frequency fn | 50-60Hz | |
| tolerance | 5% | |
| Current | ||
| Basic current(Ib) | 5A | |
| Maximum current(Imax) | 60A (100A optional) | |
| Starting current(Ist) | 0.4%Ib | |
| Active energy constant | 1000imp/kWh | |
| Measurement Accuracy | ||
| Active energy to IEC62053-21 | Class1.0 | |
| Burden | ||
| Voltage circuit | <2W <8VA | |
| Current circuit | <1VA | |
| Temperature range | ||
| Operation meter | -25℃to+70℃ | |
| Storage | -40℃to+85℃ | |
| Insulation | ||
| Insulation level | 4kV rms 1min | |
| Voltage impulse withstand | 8kV 1.2/50μs | |
| Insulation System Classification | Protective Class II | |
| Electro Magnetic Compatibility | ||
| Electrostatic discharges | ||
| Contact discharge | 8kV | |
| Air discharge | 16kV | |
| Electromagnetic RF fields | ||
| 27MHz to 500MHz typical | 10V/m | |
| 100kHz to 1GHz typical | 30V/m | |
| Fast transient burst test | 4kV | |
| Mechanical requirements | ||
| Meter shell Protection Rate | IP54 | |
| Insulation System Classification | Protective Class II | |
| Maximum cable size | 8 mm | |
Informações comerciais
- Origem
- Shenzhen, China
- Marca
- CALIN
Aplicações
- Residential and commercial electricity metering
- Utility revenue protection and AMI projects